Central Sacramento Rating & Airflow

Table RA3.1-2 Duct Leakage and Diagnostic Testing

Verification Description User Application Procedure(s)
Sealed and tested new duct systems in single family homes and townhomes Installer Testing at Final HERS Rater Testing RA3.1.4.3.1
Sealed and tested new duct systems in single family homes and townhomes Installer Testing at Rough-in, Air Handling Unit Installed RA3.1.4.3.2 RA31.4.3.2.1 RA3.1.4.3.3
Sealed and tested new duct systems in multifamily homes regardless of duct system location Installer Testing at Final HERS Rater Testing RA3.1.4.3.1
Sealed and tested new duct systems in multifamily homes regardless of duct system location Installer Testing at Final HERS Rater Testing RA3.1.4.3.4
Verification of Low Leakage Air Handler with Sealed and Tested Duct System Compliance Credit Installer Testing at Final HERS Rater Testing RA3.1.4.3.1 RA3.1.4.3.9
Verification of low leakage ducts located entirely in conditioned space Installer Testing and Inspection HERS Rater Testing and Verification RA3.1.4.3.8
Sealed and tested altered existing duct systems Installer Testing and Inspection HERS Rater Testing and Verification RA3.1.4.3.1
Sealed and tested altered existing duct systems Installer Testing and Inspection HERS Rater Testing and Verification RA3.1.4.3.4
Sealed and tested altered existing duct systems Installer Testing and Inspection
HERS Rater Testing and Verification
RA3.1.4.3.5 RA3.1.4.3.6 RA3.1.4.3.7

Alterations HERS Verification Summary Tables

Scope of Work Duct Testing
CF3R-MCH-20
Refrigerant Charge
CF3R-MCH-25
Cooling Coil Airflow
CF3R-MCH-23
Fan Efficacy
CF3R-MCH-22
Mandatory Measures
All Climate Zones
CZ's 2 , 8-15
Prescriptive Req.
Mandatory Measures
All Climate Zones
Mandatory Measures
All Climate Zones
Entirely New Split System
Equipment and Ducts (If a portion of the
replacement duct system is inaccessible, then it is
considered altered
≤ 5%
No Options
No Exceptions
Verify Charge
Verify Airflow
≥ 350 cfm/ton
≥ 350 cfm/ton
OR
Installer may demonstrate compliance using
Return Duct Sizing per Tables 150.0-B/C
≤ .45 Watts/cfm for Gas Furnaces
≤ .58 Watts/cfm for others
New Duct System or New Package Unit
≥ 75% is new ducting and the retained portions
are accessible and can be sealed
≤ 5%
No Options
No Exceptions
N/A
≥ 350 cfm/ton
OR
Installer may demonstrate compliance using
Return Duct Sizing per Tables 150.0-B/C
≤ .45 Watts/cfm for Gas Furnaces
≤ .58 Watts/cfm for others
New Small Duct High Velocity System
Equipment and Ducts
≤ 5%
No Options
No Exceptions
Verify Charge
Verify Airflow
≥ 250 cfm/ton
≥ 250 cfm/ton
OR
Installer may demonstrate compliance using Return
Duct Sizing per Tables 150.0-B/C
≤ .62 Watts/cfm
Entirely New Multi-Split
Equipment and Ducts
≤ 5% x 350 cfm/ton
nominal
No Options
No Exceptions
Verify Charge
(weigh-in only)
N/A N/A
GARAGES
Altered Ducts or System Components Located
in Garage Spaces Regardless of Duct length or
Piece of Equipment
≤ 6%
OR
≤ 10% Total Leakage
with all accessible leaks
in the garage sealed
using smoke
N/A N/A N/A
Altered Duct System
> 25' Replaced and < 75% of ducting has been
replaced
≤ 10%
W/Options
See Exceptions
N/A N/A N/A
Altered Duct System
≤ 40' Installed or located in any space
N/A N/A N/A N/A
Furnace/FAU Change-out Only
< 75% of ducting has been replaced
≤ 10%
W/Options
See Exceptions
N/A N/A N/A
Condenser or Coil Change-out Only
< 75% of ducting has been replaced
≤ 10%
W/Options
See Exceptions
Verify Charge
Verify Airflow
≥ 300 cfm/ton
N/A N/A
Refrigerant containing component
Replacement of any of the following:
Line-set, TXV, Compressor or Filter Drier
N/A Verify Charge
Verify Airflow
≥ 300 cfm/ton
N/A N/A
Package Unit
< 75% of ducting has been replaced
≤ 10%
W/Options
See Exceptions
Verify Airflow
≥ 300 cfm/ton
N/A N/A
Ductless Mini Split N/A Verify Charge
(weigh-in only)
N/A N/A
Ducted Mini Split
< 75% of ducting has been replaced
≤ 10%
W/Options
See Exceptions
Verify Charge
(weigh-in only)
N/A N/A
Ducted Multi Split
< 75% of ducting has been replaced
≤ 10% x 350 cfm/ton
W/Options
See Exceptions
Verify Charge
(weigh-in only)
N/A N/A
Exceptions to HERS Verification Requirements Below